CTH200 series PLC is a kind of automatic controller product introduced by COTRUST, which aiming at the rapidly developing OEM market in China. Fuled by the abundant experience of COTRUST engineers and the quick response to marketing demand of industry 4.0, it owns traits from rich-model to Ethernet to excellent performance. CTH200 series PLC will not just offering OEM clients with cost-effective solution of micro automation, but speed the development process of industry 4.0 in China. CTH200 is a general terms for all CPU products(nine types in all), including CPU H224, CPU H226L, CPU H224X, CPU H226XL and CPU H228XL(the CPU H228XL is just relay-output while others support both relay and transistor ). Supporting for variety of modules, such as digital I/O modules, analog I/O modules, temperature sampling modules and so on gives you flexible choice in front of industrial automation problem. CTH200 PLC communicates with computer via Ethernet port or RS485 port, and programs on MagicWorks PLC (version V2.08 or above) or MicroWin(not suit for Ethernet port). CTH200 system can be made up by one single CPU as well as one CPU with up to 7 variousoptional expansion modules. |
Performance Parameters
Physical Features |
||
Dimension(W×H×D) |
200×100×70mm |
|
Power dissipation |
15W |
|
Memory Features |
||
Program memory |
48KB,can be expand to 96K |
|
Data memory |
10KB,can be expand to 110KB |
|
Power-off protection time(super capacitor ) |
112 hours(typical) |
|
External battery (Optional) |
200 hours(typical) |
|
General Features |
||
Counters total |
256(super capacitor backup) |
|
Internal memory bits |
256(super capacitor backup) |
|
Stored permanently on power down |
112 hours(typical) |
|
Time Interrupts |
2 with 1ms resolution |
|
Edge Interrupts |
4 rising edges and/ or 4 falling edges |
|
Analog adjustment |
2 with 8 resolution |
|
Boolean execution speed |
0.15µs |
|
Float execution speed |
8µs |
|
Clock |
embedded |
|
Rated voltage |
24VDC |
|
Power supply Native and extended bus+5V +5V +24V |
1A 10mA 300mA |
|
Integrated Communication Function |
||
Communication port |
2 communication ports ,PORT0:PPI/Free port,RS485;FPORT1:PPI/freeport, RS485 PWL |
|
PPI baud rates(baud) |
9.6k,19.2k and187.5k |
|
Freeport baud rates (baud) |
1.2k ~ 115.2k |
|
Maximum cable length per segment Isolated repeater applied Isolated repeater unapplied |
When it is 1000 m, baud rate is 187.5k; when it is 1200 m, 38.4k. 50 m |
|
Maximum number of stations |
32 stations per segment,126 stations per network |
|
Maximum number of masters |
32 |
|
Point to point (PPI Master Mode) |
Yes(NWTR/NETW), 8 total, 2 reserved |
|
Ethernet Function |
||
Communication port |
1 Ethernet port |
|
Communication standard |
IEEE802.3 standard |
|
Communication speed |
10Mbps and 100Mbps self-adaption |
|
Adaptive cross connection |
Non support |
|
Interface to industrial Ethernet(10/100Mbps) |
RJ45 |
|
Protocol type |
UDP/TCP protocol Support MICO Ethernet programming, support Ethernet communication between PLC. |
|
Collocation method |
Support the upper computer through the Ethernet port search PLC, support the mouth download system configuration. |
|
Max Connections |
Each PLC supports up to 8 UDP connections and up to 4 TCP connections. |
|
The maximum number of IT connections |
8 UDP_PPI connections, with 4 master stations and 4 slave stations. 4 ModBus_TCP connections, 2 master stations and 2 slave stations. |
|
User data number |
Up to 200 bytes are used for TCP/IP transmission. Up to 240 bytes are used for ModBus_TCP transport. |
|
Port |
local:1~65535 remote server:8888 |
|
Boot time or restart time after reset |
3 seconds |
|
Indicator lamp |
Green RMC indicator: on: remote control in effect, off: remote control out Green Ethernet indicator: on: connection, flicker: transmission; out: not connected |
|
Maximum cable length |
100m |
|
Isolation |
Communication port |
|
I/O Feature |
||
Number of integrated digital inputs |
36 |
|
Input type |
Sink/Source |
|
Number of integrated digital outputs |
24 |
|
Output type |
Relay dry contact |
|
Digital I/O mapping domain |
640DI/640DQ |
|
Analog I/O mapping domain |
194AI/194AQ |
|
Maximum number of expandable I/O modules |
7 |
|
Pulse catch inputs |
24 |
|
High-speed counters Total Uniphase counters Bi-phase counters |
6 6×50KHz 4×30KHz |
|
Digital Input Features |
||
Number of integrated digital input |
36 |
|
Input type |
Sink/ Source |
|
Rated voltage |
24V DC |
|
Input voltage range |
20.4~28.8V DC |
|
Surge voltage |
35V DC,continuously 0.5s |
|
Logical 1 Signal (minimum) Logical 0 Signal (Maximum ) |
15 VDC,2.5mA 5 VDC,1mA |
|
Connect 2 wire proximity switch sensor (BERO) Allowable leakage current (maximum) |
1mA |
|
Input filter |
support 0.2ms,0.4ms,0.8ms,1.6ms,3.2ms,6.4ms,12.8ms,default 6.4ms |
|
Isolation(field side to logical circuit) Isolation groups |
500V AC,1min |
|
Simultaneous input |
36 |
|
Maximum cable length Shielded Unshielded |
500 M(standard input) 50 M(high-speed counters input) 300 M(standard input) |
|
Digital Output Features |
||
Number of integrated digital output |
24 |
|
Output type |
Relay dry contact |
|
Rated voltage |
DC:24V,AC:110V/220V |
|
Output voltage range |
DC:5~30V,AC:5~250V |
|
Output current (Max) |
2A |
|
Surge current |
5A,4s@10% duty ratio |
|
Lamp load |
DC:30W /AC:200W |
|
On resistance |
Max 0.2Ω |
|
Input delay |
Max 10ms |
|
Switching frequency(Max) |
Resistive load :10Hz Lamp load:1Hz Inductive load:0.5Hz |
|
Mechanical life cycle |
10,000,000 |
|
Contact endurance |
100,000 |
|
Simultaneous output |
24 |
|
Parallel output |
Only when the outputs are in the same group |
|
Maximum cable length Shielded Unshielded |
500m 150m |
RS485 communication port definition
Connector |
Pin |
PORT1(RS485) |
PORT0(RS485) |
|
1 |
Shell Grounded |
Shell Grounded |
2 |
+24V Grounded |
+24V Grounded |
|
3 |
RS485+signal B |
RS485+signal B |
|
4 |
Send the application |
Send the application |
|
5 |
+5V Grounded |
+5V Grounded |
|
6 |
+5V,100Ω |
+5V,100Ω |
|
7 |
+24V |
+24V |
|
8 |
RS485-signal A |
RS485-signal A |
|
9 |
NC |
NC |
|
Shell |
Shell Grounded |
Shell Grounded |
4PIN Terminal RS485 Communication port definition (CPU H228XL only)
Connector |
Pin |
Signal |
Signal definition |
|
1 |
0V |
Logically |
2 |
B |
RS485+signal B |
|
3 |
A |
RS485-signal A |
|
4 |
T |
Terminal resistance, connection terminal 3 |
Q1.What's the payment term?
A. We accept TT,LC,Western Union,Paypal.
Q2.What is the delivery time?
A. It depends on order quantity,usually it will take about 3-5 days for sample production.
Q3.What's the package used for?
A. For the small capacity,will use carton,but for big capacity,we should use honeycomb carton and pallet or wooden case for protection.
Q4.Would you accept to use our logo?
A.It's no problem,we accept OEM service.
Q5.What's your production capacity for one month?
A. Our month capacity can reach near 500-3000pcs for the most of our model.
Q6.Where is your market?
A. Our products are popular in Australia,South America,Philippines,Italy, America, Pakistan and so on.Some of them are our regular customers and some of them are developing. We hope you can join us and make mutural benifit from our cooperation.
Q7. What kind of certificates you have?
A. Our company has ISO9001,CE, RoHS,SGS etc.