Customization: | Available |
---|---|
Task: | Program |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1. The PROFINET bus communicates at a rate of 100 Mb Ps, and the communication distance from station to station can be up to 100 meters (100BASE-TX);
2, topological structure support star, tree, linear, ring structure;
3. Each slave station is allowed to expand 8 I/O modules (digital quantity module, analog quantity module, temperature module, HSC, HSP, excluding CAN module /ECT slave station module).
4. Supported Siemens PROFINET master station, including Siemens S7-300, Siemens S7-400, Siemens S7-1200, Siemens S7-1500;
5. Configuration software TIA Portal V13 and higher.
Physical properties |
|
Size(W×H×D) |
34×115×100mm mm |
Power loss |
|
Rated input voltage |
24V DC |
Input voltage range |
20.4V~28.8V DC |
Input current |
0.8A |
Bus power supply voltage |
+5V DC |
Bus supply current |
1.6A |
Isolation |
External power supply is isolated from system power supply |
Power protection |
The power supply end provides the reverse connection protection function and the surge absorption function |
LED indicator characteristics |
|
24V power indicator (green) |
ON = 24VDC power supply is normal |
OFF = No 24VDC power supply |
|
SF indicator light (red) |
ON = extended I/O bus failure or PROFINET module failure |
OFF = No error |
|
BF indicator light (red) |
ON = PROFINET bus communication failure (no connection to switch, no network detected) |
Blinking=Inconsistent hardware configuration |
|
OFF = No error |
|
MT indicator light (yellow)(Maintenance indicator light)
|
Reserved |
Indicator light (green) |
ON = There is a connection to the switch /PN master |
OFF =No connection to switch /PN master |
|
Indicator light (yellow) |
ON = data receiving and receiving to switch /PN master station |
OFF = No data transceiver to switch /PN master station |
EetendI /O capabilities |
|
Maximum number of modules supported per slave |
8(can be added digital , analog and temperature module, HSC,HSP module, other types of module are not included) |
Protocol type |
CTH300 PLC custom 55MHz bus protocol |
Topology |
Support star, tree, linear, ring |
PROFINET communication port |
|
Communication port |
1 dual RJ45 port |
Data transmission rate |
Ethernet with a transmission rate of 10Mbps |
The PROFINET transmission rate is 100Mbps, full duplex |
|
Supported Ethernet services |
Ping, ARP, Network Diagnostic (SNMP)/MIB-2, LLDP |
Sending cycle |
250us~4ms |
Third-party PROFINET master station |
Support |
Longest communication distance from station to station |
100m(100BASE-TX) |
Topology |
Supports star, tree, linear and ring topologies |
Isolation |
Communication port isolation |
Hardware configuration function |
|
Import file type |
Profinet GDS file XML format |
Third-party PN master station |
The addition of the CTH3 PNT-000S1 module supports the expansion of 8 slots |
Expansion module can add digital, analog and temperature module, HSC,HSP module, other types of module are not included |
Q1.What's the payment term?
A. We accept TT,LC,Western Union,Paypal.
Q2.What is the delivery time?
A. It depends on order quantity,usually it will take about 3-5 days for sample production.
Q3.What's the package used for?
A. For the small capacity,will use carton,but for big capacity,we should use honeycomb carton and pallet or wooden case for protection.
Q4.Would you accept to use our logo?
A.It's no problem,we accept OEM service.
Q5.What's your production capacity for one month?
A. Our month capacity can reach near 500-3000pcs for the most of our model.
Q6.Where is your market?
A. Our products are popular in Australia,South America,Philippines,Italy, America, Pakistan and so on.Some of them are our regular customers and some of them are developing. We hope you can join us and make mutural benifit from our cooperation.
Q7. What kind of certificates you have?
A. Our company has ISO9001,CE, RoHS,SGS etc.
OEM Services
Logo
Please offer us your own high resolution logo in JPG format,there should be two colors at most in the logo and there should be no gradient effect in the logo.
2. Label
Please offer us your own model numbers.
Lead Time
1.Sample orders will be delivered from our factory within 3-5 working days.
2.General orders will be delivered from our factory within 7-15 working days.
3.Large orders will be delivered from our factory within 45 working days at most.
Shipment
1.By EMS,DHL,FedEx,TNT,UPS or other Express.
2.By our forwarding agent(by Air or by Sea).
3.By your own forwarding agent.