Basic Info.
Model NO.
CTH2 216-2BX35-0X40
Certification
RoHS, ISO: 9001, CE
Specification
196.5*80*62mm
Product Description
Order Data
Products data | Order No. |
CTH200 V5 series CPU |
CPU H226XL V5 version | 72KB program memory,110KB data memory,220VAC power supply,24DI/16DQ relay output,2A,2 PPI port/ FPORT,1 Ethernet port.Data permanent stored.Support Analog,CAN and RS485 expansion boards. | CTH2 216-2BX35-0X40 |
Performance Parameters
Physical Features CTH2 216-2BX35-0X40 |
Dimension(W×H×D) | 196.5×80×62mm |
Power dissipation | 11W |
Memory Features |
Program memory | 24KB+48KB |
Data memory | 10KB+100KB |
General Features |
Timers total 1ms 10ms 100ms | 512 4 272 236 |
Counters total | 256 |
Internal memory bits | 256 |
Stored permanently on power down | Data permanent stored |
Sequential control relay (S) | 256 |
Time Interrupts | 2 with 1ms resolution |
Edge Interrupts | 4 rising edges and/ or 4 falling edges |
Analog adjustment | Non |
Boolean execution speed | ≤0.15µs |
Float execution speed | ≤8µs |
Clock | embedded ,precision ±120s/m |
BD expansion board interface number | 1,Support CAN expansion board, analog expansion board |
System indicator | 5,STOP,RUN,SF,RMC,LINK/ACT |
RUN/STOP dial code | Yes,2 |
Battery card interface | Support,power supply below 2V,alarm bit SM195.0 |
Programming card and Memory card | Support |
Rated input voltage | 85-264VDC(47-63HZ) |
Power supply Native and extended bus+5V +24V | 660mA 200mA |
Integrated Communication Function |
Communication Interface | 2 communication ports ,PORT0:PPI/Free port,RS485;FPORT0:PPI/Free port,RS485 After plugging in the RS485 expansion board and restarting, PORT0 (RS485, PPI communication port) PORT1 (RS485, PPI/ free communication port), FPORT0 (free port) |
PPI baud rates(baud) | 9.6k,19.2k and 187.5k |
Freeport baud rates(baud) | 1.2k ~ 115.2k |
Maximum number of sations | 32 stations per segment,126 stations per network |
Maximum number of masters | 32 |
Point-to-point (PPI master station mode) | Yes(NETR/NETW), maximum 8 connections, and each connection has a maximum communication of 200 bytes |
MPI connect | (1PG/1OP) 8 in total, 2 reserved |
Maximum cable length Isolated repeater applied Isolated repeater unapplied | When it is 1000 m, baud rate is 187.5k; when it is 1200 m, 38.4k. 50m |
Ethernet Function |
Communication port | 1 Ethernet port |
Communication standard | IEEE802.3 standard |
Communication speed | 10Mbps and 100Mbps self-adaption |
Adaptive cross connection | Non support |
Interface to industrial Ethernet(10/100Mbps) | RJ45 port |
Protocol type | UDP/TCP protocol Support PDP_PPI, MODBUS_TCP, Socket, S7 protocols, support PLC Ethernet communication, support MiCo Ethernet programming. |
Collocation method | Support the upper computer through the Ethernet port search PLC, support the mouth download system configuration. |
Application interface | Support MiCo service, UDP_PPI, Modbus_TCP, S7 protocol, Socket programming.Support Ethernet port online firmware upgrade function. |
Maximum number of connections | 8 UDP_PPI, no master or slave 8 Modbus_TCP, no master or slave 4 Socket connections, 2 UDP, 2 TCP 8 S7 protocol, no master and slave, COTRUST PLC only as slave station |
User data number | Up to 200 bytes for UDP_PPI transmission. Up to 240 bytes are used for ModBus_TCP transmission. A maximum of 512 bytes is used for Socket transmission Up to 200 bytes for S7 transmission |
Port | local:1~65535 remote server:8888 |
Boot time or restart time after reset | 3 seconds |
Indicator lamp | Green RMC indicator: on: remote control in effect, off: remote control out Green Ethernet indicator: on: connection, flicker: transmission; out: not connected |
Maximum cable length | 100m |
Isolation | Communication port isolation |
Integrated Communication Function (CANopen) - use for CAN communication board model CTH2-CAN-01S2-EB |
Communication Interface | 1(8 Pin) |
Communication speed (kbps) | 1000 | 800 | 500 | 250 | 150 | 50 | 20 |
Maximum cable length(m) | 25 | 50 | 100 | 250 | 500 | 1000 | 2500 |
Maximum station address quantity | 127 |
Station address range | 1-127 |
Maximum number of master stations connect to slave stations | 32 |
Collocation method | CAN configuration blocks and EDS files |
Maximum digital access | Nomal IO | CANopen IO |
| Byte | Memory starting address | | Byte | Memory starting address |
Input | 16 | IB0 | Input | 64 | IB16 |
Output | 16 | QB0 | Output | 64 | QB16 |
Maximum analog access | Nomal IO | CANopen IO |
| Channel | Memory starting address | | channel | Memory starting address |
Input | 32 | AIW0 | Input | 162 | AIW64 |
Output | 32 | AQW0 | Output | 162 | AQW64 |
Integrated Communication Function (CANopen) - use for CAN communication board model CTH2-CAN-01S2-EB |
Protocol | CanFree |
Use method | Supported by internal library instructions |
I/O Features |
Number of integrated digital inputs | 24 |
Input type | Sink/Source |
Number of integrated digital outputs | 16 |
Output type | Relay,dry contact |
Digital I/O mapping domain | 640DI/640DQ |
Analog I/O mapping domain | 194AI/194AQ |
Maximum number of expandable I/O module | 7 |
Maximum digital I/O configuration | 128DI/128DO |
Maximum analog I/O configuration | 32AI/32AQ |
Pulse catch inputs | 24 |
High-speed counters Total Uniphase counters Bi-phase counters | 6 6×50KHz 4×30KHz |
Digital Input Features |
Number of integrated digital input | 24 |
Input type | Sink/ Source |
Rated voltage | 24V DC |
Maximum continuous permissible voltage | 30V DC |
Logical 1 Signal (minimum) Logical 0 Signal (Maximum) | 15 VDC,2.5mA 5 VDC,1mA |
Isolation(field side to logical circuit) | 500V AC,1min |
Simultaneous input | 24 |
Maximum cable length Shielded Unshielded | 500 M(standard input) 50 M(high-speed counters input) 300 M(standard input) |
Digital Output Features |
Number of integrated digital output | 16 |
Output type | Relay,dry contact |
Rated voltage | 24VDC or 110V/220VAC |
Output voltage range | 5~30VDC and 5-250VAC |
Logical 1 Signal (minimum) | - |
Logical 0 Signal (Maximum) | - |
Rated current per point | 2A |
Rated current for each common point | 8A |
Leakage current (maximum) | - |
Surge current(Maximum) | 7A |
Lamp load (maximum) | 30W DC/200W AC |
On resistance (contact) | 0.2Ω |
Isolation(field side to logical circuit) | - |
Delay | Off to on:- on to off:- |
Contact life at rated load | 100000 times on and off |
Simultaneous input | All output point |
Parallel output | Only when the outputs are in the same group |
Maximum cable length Shielded Unshielded | 500m 150m |
* Support new V2 programming card
* Ultracapacitors power-off protection time 10 hours and extended batteries for 200 days
* Alarm function for insufficient battery power of the battery card: when it is lower than 2V, the alarm bit SM195.0
Wiring diagram
RS485 communication port definition
Connector | PIN | PORT0(RS485) | FPORT0(RS485) |
| 1 | Shell Grounded | Shell Grounded |
2 | logically | logically |
3 | RS485+signal B | RS485+signal B |
4 | Send the application RTS | Send the application RTS |
5 | logically | logically |
6 | +5V, series connection 100 Ω resistance | +5V, series connection 100 Ω resistance |
7 | +24V | +24V |
8 | RS485-signal A | RS485-signal A |
9 | NC | NC |
shell | Shell Grounded | Shell Grounded |
RS485 expansion board communication interface
Module interface and connector | PIN | FPORT0(RS485) |
Note:when terminal resistors are needed, short connect the 2 and 3 pins | 1 | RS485+signal B |
2 | RS485-signalA |
3 | Terminal resistance |
4 | Shell Grounded |
5 | RS485 signal GND |
6 | NC |
7 | NC |
8 | NC |
9 | NC |
Address:
9/F, Block a Building 6, Shenzhen International Innovation Valley, Dashi 1st Road, Nanshan District, Shenzhen, Guangdong, China
Business Type:
Manufacturer/Factory
Business Range:
Electrical & Electronics, Industrial Equipment & Components, Manufacturing & Processing Machinery
Management System Certification:
ISO 9001, HSE
Company Introduction:
COTRUST Technologies Co., Ltd founded in 2003, is dedicated to R&D, manufacturing and sales of industrial automation control products. Relying on high quality, high performance automation control products and solutions to create maximum value for customers, determined to become the world′s leading industrial automation solutions supplier.
As a high-tech enterprise, COTRUST provides a wide business coverage of intelligent equipment & robot, new energy vehicles, industrial Internet, smart factory. Main products include PLC, Motion control&servo drive, HMI, dedicated control system and automation software MagicWorks programming software (PLC/HMI/TUNER/OPC), the new launch MiCo remote solution, multi-robot cooperative control system widely used in customer solutions.
COTRUST built a long-term partnerships with customers. To achieve this, COTRUST offers more than just products: Working with COTRUST gives customers access to leading integrated manufacturing and R&D facilities, as well as highly skilled engineering and industry specialists.
COTRUST invests 10% of revenues and 40% of employees in R&D, owned more than 30 trademark registration and 79 patents with certificates( including invention, utility models and appearance). Uses a uniquely rigorous engineering process that incorporates advanced design modelling, performance analysis and quality assurance techniques for improve production capacity continuously and promote sustainable development.
On the basis of owning industrial automation technologies with proprietary intellectual property rights, COTRUST perseveres in industry marketing and providing total solution to customers in segment market and achieves growth of both enterprise value and customer value.